Passing valve screening check
A short screening check. It suggests the likely cause and the next step to confirm it. No data is collected or sent anywhere.
Step 1
Is the valve fully closed, with signs of flow downstream (pressure rise, flow reading or noise)?
The full screening path in plain text
- Screen first, then confirm. Close the valve fully. Watch downstream pressure, flow and sound. These signs suggest passing. Confirm with a proper seat test, such as pressure decay or a bleed check.
- Check the gates. Injection needs fittings in good condition, a valve design that suits it, and permission from operations. Without these, get an assessment first.
- If the valve is also hard to operate: screening points to debris and dried deposits. Where the gates pass, cleaner injection and careful cycling is the usual first step. Test the seat again after.
- If it moves freely but still passes: screening points to seat surface damage or lost sealant. In suitable valves, cleaner then controlled sealant injection can restore the seal.
- If correct injection has already failed, or damage is severe: sealant cannot bridge large damage. Plan repair or replacement, and take specialist advice on interim isolation.
The full background is in our guide: Passing valves: why a closed valve still leaks.